“How many HP is this unit?” is one of the least useful questions in heat pump selection. Two units both rated at 5 HP can differ by more than 30% in heating output at −20°C. These five parameters are what really decide winter performance.

Nominal heating capacity is not low-temperature heating capacity

The “rated heating capacity” in a brochure is usually measured at 7°C ambient and 35°C water outlet. In a northern winter the outdoor temperature may reach −15°C or lower, and output drops noticeably.

Select on output at −12°C and −20°C, not only on the 7°C figure. Take the Lanfeng DXL12ID: 13.0 kW rated heating at 7°C, 10.5 kW nominal heating at −12°C, a gap of about 19%. Comparing low-temperature output with the building heat load is what makes selection work.

What COP and IPLV(H) each tell you

COP is instantaneous efficiency at one operating point; a good number does not mean the unit is efficient all year. IPLV(H) is the integrated part-load value, which is closer to real average efficiency in use.

For heating units, look first at low-temperature COP and IPLV(H), then estimate annual running cost against local electricity prices and operating hours. Choosing purely on peak COP invites confusion with laboratory numbers.

Defrost logic decides whether winter is comfortable

In cold, humid regions frosting on the evaporator is unavoidable. The real question is not whether frost forms, but when it is cleared, how clean the defrost is and where the water goes.

Good control logic weighs coil temperature, ambient temperature and humidity, and runtime together, so it defrosts when there is frost and does nothing when there is none. Confirm the drainage route for defrost water, so it does not freeze, block or split the pipework.

Terminal water temperature and flow define comfort

Underfloor heating needs 35–45°C low-temperature water, fan coils usually need 45–50°C, and radiators may need 55°C or more. Different terminals mean completely different unit selection and control strategy.

Work out water flow and pump head as well. However capable the unit, insufficient flow leads to large temperature differences, frequent cycling and higher noise.

TerminalTypical flow temperatureCharacteristics
Underfloor heating35–45°CComfortable and efficient, slow to warm up
Fan coil45–50°CFast response, heating and cooling in one
Radiator55°C and aboveCommon in retrofits, needs a high-temperature model
Pool heating28–30°C pool waterNeeds corrosion protection and water quality interlock

Electrical capacity and starting current: check before installation

In northern townships and older housing estates, single-phase supply is often insufficient. Before selection, confirm the incoming capacity, cable size and whether three-phase power is available.

Full DC inverter units have gentler soft-start behaviour, but total current still has to be calculated when several units run in parallel. Where necessary, add thermal storage or staggered operation, so units do not start at the same time as other high-power equipment.